Grounding and bonding: the three paths of the DS3 and what the NEC asks
The manual's three grounding paths, the racking grounded per local code, NEC 690.41 to 690.47 and Article 250 in the edition your AHJ enforces, and what low voltage does not buy you.
What stays from the lesson, to keep at hand before you close out the grounding. The page numbers in the sources are the PDF pages of each document; the NEC is cited by edition.
What this lesson solves
- The manual gives three ways to connect grounds: the PE wire embedded in the trunk cable, which grounds the micros in the AC circuit box; the grounding washer, which bonds the micro to a grounded rack and grounds the rack through grounded micros; and an external wire on the grounding lug.
- The racking is grounded per local electrical codes, and NEC 110.3(B) makes the manual binding: listed equipment is installed and used per its listing instructions. The 2026 edition adds that those instructions cannot override the code.
- NEC 690.43: exposed metal parts of module frames, equipment and enclosures are grounded regardless of voltage. Frames and rails are bonded with listed devices; the micro's washer bonds the micro, not the whole array.
- The equipment grounding conductor is sized by Table 250.122: 12 AWG copper with a 20 A breaker, 10 AWG with a 30 A breaker (the 60 A row), never smaller than 14 AWG in the 2017 text. It is bare, green or green with yellow stripes, a color used for nothing else.
- Low voltage is the manual's argument, not an exemption: the NEC grounds metal regardless of voltage, the warning forbids touching live parts once the system is on the grid, and the array supplies DC whenever it sees light. It saves only the DC arc-fault device, required from 80 V DC.
The numbers in this lesson, with sources
| What | Value | Fact |
|---|---|---|
| Ways to connect grounds on the DS3 | 3 | 6.10 |
| EGC, copper, with a 20 A / 30 A breaker | 12 AWG / 10 AWG (60 A row) | 9.77 |
| Smallest EGC, NEC 2017 690.45 | 14 AWG | 9.77 |
| EGC run apart from the circuit, without raceway or armor | 6 AWG or larger | 9.78 |
| Single rod standing alone | 25 ohms or less to earth | 9.81 |
| Ground rods | at least 8 ft (2.44 m) long; 6 ft (1.8 m) apart | 9.82 |
Each value comes from the course fact base, with the document page or the code section on record.
Chapters
- Intro0:00
- 1The three grounding paths1:19
- 2What the manual requires2:54
- 3The trunk cable and the green3:57
- 4What the NEC asks of the array5:43
- 5Bonding in practice9:06
- 6The grounding electrode9:45
- 7The safety argument11:03
- 8What low voltage doesn't buy you11:48
- 9The common mistake14:13
- 10Quick check14:59
- 11Checklist and next lesson15:36
Preview transcript
920 wordsThis is the text of the open part of this lesson. The full transcript comes with the course, along with the job site materials.
Intro
0:00Micro on the rail, trunk cable laid out, and here comes the question nobody likes to answer on the roof. How does this micro get grounded? The manual gives three paths, and the NEC asks for more. Hi, I'm Sol. This is lesson one point three, still mechanical installation. And I'm Helios. I bring the ground wire question, and what the inspector will look for. The topic is grounding, bonding the metal parts, and the safety argument of the micro. By the end, you'll ground the DS3 by the manual's three paths, and know which one fits. And I want to know what the NEC asks of the array, on top of the micro. Bonded metal parts, an equipment grounding conductor sized by the code, and a grounding electrode system. Where do we start? The manufacturer's manual, or the code? The manual: the three paths and what it requires. Then the code, the electrode, and the safety argument. And we close with what the low voltage on the roof doesn't buy you. That part's on me.
The three grounding paths
1:19Chapter one. The DS3 Series user manual, revision two point three, page twelve, step four. Three ways to connect grounds on the DS3, it says. Path one: the trunk cable has an embedded PE wire, and it grounds the micros in the AC circuit box. PE is the manual's word. On a US job, that's the equipment grounding conductor, the EGC, or just the ground wire. It's the green conductor of the trunk cable, the same one that lands on the ground bar. Path two: if the rack is grounded, the grounding washer on the micro can create a tight bond onto the rack. And it also grounds the rack through the micro, when the micros are grounded. So that path works both ways, depending on which side is already grounded. Path three: if an external connection is needed, an external wire is bonded to the grounding lug outside the micro, and run to ground. The manual's figure numbers all three: the trunk cable connector, the washer on the rack, and the lug outside the case. Two routes end at the same ground: the micro's, and the bonding of the array metal. One does not replace the other. The micro goes through the trunk cable or the washer. Frames and racking go through their own bonding. To choose, the manual sets the condition: the washer needs a grounded rack; the external wire, when an external connection is needed.
What the manual requires
2:54Chapter two. Back one page, to page eleven, at the end of the warning: the racking must be grounded per local electrical codes. And the local electrical code here has a name: the NEC, in the edition your AHJ enforces for that permit. Right. And the NEC makes the manual binding. Section one ten point three B: listed equipment is installed and used per the instructions in its listing or labeling. And the twenty twenty-six edition adds that those instructions can't override the code. So installing against the manual is also a code problem. The quick guide repeats it on one sheet. First, the racking grounded per local electrical codes. Then step four, with the same three ways, numbered. And the installer FAQ on the US site adds one line: check your local regulations, or the AHJ, for proper grounding.
The trunk cable and the green
3:57Chapter three. Manual, page eleven, step two: the conductors of the trunk cable. L one, black; L two, red; and PE, green. Three conductors, and no neutral. And the manual warns: color codes may vary with local regulations, so check that every wire matches before connecting. The step eight drawing shows it: black and red to a two-pole breaker, green to the ground bar. And from the bar, to ground: that symbol at the bottom. What that ground is, we see in chapter six. On a US job, the local rule is the NEC. Section two fifty point one nineteen, in the twenty seventeen text. The equipment grounding conductor is bare, or green, or green with yellow stripes. And that color is used for nothing else. Green is ground, period. The neutral, where there is one, is white or gray. The DS3 trunk cable has no neutral. And a house rule: from the junction box to the panel, the line conductors are never white, gray, or green. And L one and L two are marked the same way at both ends. And the ground is the first to connect and the last to let go. Manual, page three. When connecting, the AC connector goes first, so the micro is grounded, and then the DC. And when disconnecting? Open the branch circuit breaker first, keep the ground conductor connected to the micro, and then disconnect the DC.
What the NEC asks of the array
5:43Chapter four. The manufacturer's manual steps aside, and the NEC comes in: article six ninety, sections six ninety point forty-one to forty-seven. Six ninety point forty-one first: the DC side of the array, its grounding configuration and its ground-fault protection. And where does the DS3 fit there? Our reading. The datasheet says high frequency transformers, galvanically isolated. And the manual says the micro has an integral ground-fault detector and interrupter, the GFDI. So each input is an isolated PV source, with the micro's own ground-fault protection. You add no DC grounding to the module leads. Six ninety point forty-three: exposed metal parts of module frames, equipment, and conductor enclosures are grounded, regardless of voltage. Regardless of voltage. That line answers the guy who says sixty volts doesn't need a ground.
Job site materials in every lesson, questions inside the video, spaced review, a final exam and a certificate of completion with a public verification code. 7 days to cancel, with a full refund.