Lesson 2.1preview: 5:58full lesson: 15 min

The two inputs: one module on each, and the voltage and current math

One module per input, the three voltage lines, the cold check against 60 V, the current lines of the DS3-S, DS3-L, DS3 and DS3-H, and the mistake that voids the warranty.

Every page cited is the page of the document's PDF file, not always the number printed on the page.

What this lesson solves

  • Two inputs with independent MPPT, one module on each: its plus and its minus together, on the same input.
  • The cold check: one module's Voc, corrected with its coefficient for the site's lowest expected ambient temperature, against the 60 V ceiling, which fails a module on safety; the 28 V to 45 V window fails it only on energy.
  • Current follows the model: operating current against the maximum input current, short-circuit current against the short circuit line of your model.
  • The DS3 is an interactive inverter in NEC 2017 Article 100, not an AC module; with one module per input, the NEC 2017 690.9(A) Exception asks for no DC fuse.

The numbers in this lesson, with sources

WhatValueFact
Peak power tracking voltage (MPPT window)28 V to 45 V2.3
Operating voltage range26 V to 60 V2.4
Maximum input voltage, the ceiling60 V2.2
Max input current: DS3-S, DS3-L, DS3, DS3-H16, 18, 20 and 20 A × 22.5
Max input short circuit current, same order20, 22.5, 25 and 25 A per input2.6

Each value comes from the course fact base, with the document page or the code section on record.

Chapters

  1. Intro0:00
  2. 1The two inputs1:14
  3. 2The three voltage lines2:29
  4. 3The cold check4:31
  5. 4Current, model by model6:32
  6. 5The wire in the NEC8:48
  7. 6What doesn't exist here9:50
  8. 7An input left empty11:10
  9. 8The common mistake12:03
  10. 9Quick check13:18
  11. 10Checklist and next lesson13:47

Preview transcript

773 words

This is the text of the open part of this lesson. The full transcript comes with the course, along with the job site materials.

Intro

0:00

Module picked, micros on the rail, trunk cable clicked in. Now it's time to plug in the DC. And this is where one lead on the wrong input damages the micro and voids the warranty. Hi, I'm Sol. This is lesson two point one, on the DC side. And I'm Helios. I bring the real wiring, and the question from the roof. The topic is the connection: how many modules go on each input, and the math that approves them. With the manufacturer's page on screen, and the NEC right next to it. By the end of this lesson, you'll connect the two inputs and run the voltage and current check for each model. And I want to know what happens when the plus and the minus of one module split up. Here's the route: the two inputs, the three voltage lines, the cold check, and the current, model by model. Then what the code says about that wire, what doesn't exist here, the empty input, and the mistake that costs a micro. Chapter one. The user manual for North America, revision two point three, page eight, the key product features.

The two inputs

1:14

First line: one microinverter connects to two solar modules. Third line: two independent input channels, with MPPT. Channels? On the roof I call them inputs. Same thing. What the manual calls input channels, we call inputs: two of them, with one module on each. The datasheet's wiring schematic draws it: each micro with two modules, one on each input. Two pairs of connectors. One pair per module, with its plus and its minus together. And what does independent change for me, once the job is done? Each input tracks the maximum power point of its own module, regardless of the other one. The manual says maximum peak power tracking. In the field, it's maximum power point tracking, MPPT. And in the EMA portal, the module view shows the power of each panel. So a shaded module shows up on its own, without dragging its neighbor down.

The three voltage lines

2:29

Chapter two. The DS3 Series datasheet for the USA and Canada, page two, the input data. You met these three lines in lesson zero point four. They look alike on paper, and each one has a different job. Peak power tracking voltage, the MPPT window: twenty-eight to forty-five volts. That's the window where the micro hunts for the module's maximum power point? Right. And that window fails a module on energy, not on safety. Fails it how, if nothing gets damaged? The manual asks that the module's operating voltage range sit inside the micro's input range. House rule, applied to the tracking window: in the site's heat, the module's working voltage stays above twenty-eight volts. In the cold, below forty-five. Outside that window, nothing breaks. The micro just stops finding the best point, and the energy drops. And where do I confirm that a module falls inside? In E-decider, the module compatibility tool the manual names, or with your local APsystems technical support. Second line. Operating voltage range: twenty-six to sixty volts. And what does that one describe? Its last number is the same as the ceiling. It's the whole window the input works in. Below twenty-six volts, the micro doesn't even start. Third line. Maximum input voltage: sixty volts. That's a limit, not a window. Two ranges and one ceiling. And the ceiling is what fails a module in the cold. And page three gives the DS3-H the same three lines. The voltage math is the same on all four models. I carry that table printed. The operating range and the ceiling are not the same line.

The cold check

4:31

Chapter three. Manual, page twenty-one, the third warning of the technical data. The maximum open circuit voltage of the PV module must not exceed the specified maximum input voltage. That sentence talks about one module. And each input gets one module. It fits. It fits. The math is one module against the sixty-volt ceiling. At what temperature? The module datasheet gives that voltage at seventy-seven degrees. At the site's lowest expected temperature. Cold pushes the open circuit voltage up. Generic example, with numbers from the module's own datasheet, not from the micro's. Open circuit voltage: forty-one volts, at seventy-seven degrees Fahrenheit, twenty-five Celsius. Coefficient of that voltage: minus zero point two seven percent per degree Celsius. Example low at the site: thirty-two degrees Fahrenheit, zero Celsius. That's twenty-five degrees Celsius below the test temperature. Twenty-five times zero point two seven: six point seven five percent more. Forty-one volts becomes forty-three point eight. Plenty of margin. And a module of fifty-six volts open circuit, at the same example site?