Field diagnosis: shade, grid trips, the solid red and the swap
The shade that repeats, the micro that protects itself from the grid, the utility's trip settings, the breaker that keeps tripping, the DC ground fault, and the swap of a micro by the U.S. manual.
What to keep from the lesson. Page numbers in the sources are the PDF pages of each document.
What this lesson solves
- Low power at the same hour every day is shade from an obstacle, such as a tree, a dormer or a pole: normal behavior, until the obstacle is removed.
- A micro that drops out and comes back can be in AC protection mode; the trip settings are the utility's, and the applied profile goes against its document.
- A tripped breaker is reset only after it is determined that the circuit can be safely energized, never reclosed again and again.
- Solid red is a DC ground fault (GFDI): branch locked and tagged, photos of the cables and connectors, and APsystems technical support clears the error.
- No swap before the RMA. The swap follows the safety page, AC connector first in and last out, and ends with Replace in the EMA, never delete and add.
The numbers in this lesson, with sources
| What | Value | Fact |
|---|---|---|
| Default trip above 1.10 × nominal, Category III | 13 s | 18.10 |
| Default trip above 1.20 × nominal | 0.16 s | 18.10 |
| Default trip below 0.88 × nominal | 21 s | 18.10 |
| Default trip below 0.50 × nominal | 2 s | 18.10 |
Each value comes from the course fact base, with the document page or the code section on record.
Chapters
- Intro0:00
- 1The shade that repeats1:37
- 2Grid protection3:12
- 3Record and report6:49
- 4The breaker that keeps tripping8:05
- 5The solid red: a DC ground fault9:10
- 6The swap, by the U.S. manual10:53
- 7The common mistake15:05
- 8Quick check15:50
- 9Checklist and next lesson16:21
Preview transcript
940 wordsThis is the text of the open part of this lesson. The full transcript comes with the course, along with the job site materials.
Intro
0:00The micro drops out around noon, comes back on its own, and the homeowner already wants it replaced. Above one point one times nominal voltage, the IEEE 1547 default asks for a trip within thirteen seconds. That micro is doing its job. Hi, I'm Sol. This is lesson six point three, the second half of field diagnosis. And I'm Helios. Today I bring the portal's protection data, and a replacement micro in the truck. Today it's the micro that produces less, the one that drops out, the solid red LED, and the swap. And next to the manufacturer's papers, the utility's rules. They decide where the micro trips. By the end of this lesson, you'll tell shade from a fault, read a micro that protects itself, and swap a micro by the manual. And I want to know what I measure, what I write down, and who gets the report when it's the grid. Lesson six point two read the signal, the network, the ECU, and the grid. What comes next? Production that drops or cuts out: the shade, and the micro that protects itself from the grid. Then what I write down and report, and the breaker that keeps tripping. And at the end, the solid red LED and the swap of a micro, by the U.S. manual.
The shade that repeats
1:37Chapter one. Troubleshooting guide, page twenty-two: low power, on some inverters. The first line is shade: a repetitive pattern, at the same hour of the day. And that's when somebody climbs up to swap the micro, sure it's a fault. The guide calls it normal behavior. The low power stays until the obstacle is removed. And it names the obstacles: a tree, a dormer, an electrical pole. And the same obstacle hits harder or softer depending on the time of year. Before calling it a fault, open the module view. EMA website manual for installers, page eight: daily, or over the last thirty days. And page nine: the time marker. Drag it across the timeline, and the panels show the power at that time. Same panel, same hour, low every day? That's shade, not the micro. Back to page twenty-two. It also lists three causes you already know: AC protection mode, zero export, and loose connections. Loose connections, DC and AC, get checked thoroughly. That's the guide's word. And a connector opens only with the branch locked and tagged open. Before it opens, the absence of voltage on the branch is verified, backfeed included. And zero export belongs to the ECU-C. We don't use it with the DS3 Series.
Grid protection
3:12Chapter two. Now the micro that drops out on its own and comes back on its own. Same guide, page eighteen, point four: the micros may be in AC protection mode. Against large swings of the utility grid, or high temperature, over a hundred degrees Celsius. And they resume producing as soon as the grid settles or the temperature drops. Drops out, comes back. That's the protection the guide describes. The portal keeps the trail. EMA website manual for installers, page thirty-nine: protection data. When the customer's system is abnormal, there's protection data there, for checking out the fault. And on the same page, intelligent diagnosis: the system status, with recommendations when it isn't healthy. And page fifteen, inverter data: the grid parameters of each micro, with AC volts, frequency, and temperature. We saw this in lesson six point two: the logged voltage goes against the applied profile, not the datasheet window. And the window itself, from lesson four point four: datasheet, page two, read as zero point eight eight to one point one zero times nominal. That's the continuous band of IEEE 1547, Category three. Where the micro actually trips is another number. And note one: the range can be extended beyond nominal, if the utility requires it. So who picks the numbers? The utility, as guided by the authority that governs interconnection. It specifies the categories and the settings. The IEEE 1547 defaults, Category three, as utilities publish them. Above one point one times nominal: thirteen seconds. Above one point two: zero point one six seconds. Below zero point eight eight: twenty-one seconds. Below one half: two seconds. Frequency, the same in the three categories: above sixty-one point two or below fifty-eight point five hertz, three hundred seconds. Above sixty-two or below fifty-six point five, zero point one six seconds. And not every utility takes the default. Massachusetts trips at one point one times nominal in two seconds. And after a trip, the default delay to enter service is three hundred seconds. Rule twenty-one asks for fifteen. That's why it takes a while to come back. With the grid stable again, it waits out its profile's delay. Your system's numbers live in the applied grid profile. EMA Manager manual, page sixty-four: selected when installing the system. Pick one that isn't adequate for your region, and the inverters may not start, or may not produce as they should. And this screenshot is a fifty-hertz grid from another region. It shows where the settings sit, not reference values. We saw the rule in lesson six point two: each setting against the utility's document, and never a window widened by eye. And the case from that lesson: a two-forty setting on a two-oh-eight service. At normal voltage, the micros don't produce.
Record and report
6:49Chapter three. The manual's first step, page eleven: verify that the grid voltage matches the microinverter rating. We saw the measurement in lesson six point two: at the panel, on the utility side, by a qualified person, with the protection for live work. And on a trip, what do I write down?
Job site materials in every lesson, questions inside the video, spaced review, a final exam and a certificate of completion with a public verification code. 7 days to cancel, with a full refund.