LED, communication and production: the two failure trees

The six LED states of the DS3, the steady red, what the FAQ adds, and how to tell the data that stop arriving from the energy that stops flowing.

What to keep from the lesson. Page numbers in the sources are the PDF pages of each document.

What this lesson solves

  • The LED color talks about energy and the speed about communication: slow is a 5 s gap; fast is a 2 s gap, with no ECU communication for over 60 min.
  • At startup, ten short green blinks; after a DC reconnection, a quick red comes first. The manuals govern over the sheet that writes three.
  • Steady red is the GFDI error, a ground fault on the DC side: branch locked and tagged before any connector opens, and APsystems technical support clears the error.
  • Two families: a communication issue, micros producing and data not arriving (NC); a production issue, low or no power (0 W or 2 W).
  • Losing communication is not losing production; when only some micros are affected, check again after a couple of hours.

The numbers in this lesson, with sources

WhatValueFact
Slow green, 5 s gapproducing, and communicating with the ECU13.2
Slow red, 5 s gapnot producing13.3
Fast green, 2 s gapno ECU communication for over 60 min, still producing13.4
Fast red, 2 s gapno ECU communication for over 60 min, not producing13.5

Each value comes from the course fact base, with the document page or the code section on record.

Chapters

  1. Intro0:00
  2. 1The start: ten green blinks1:25
  3. 2The two slow blinks2:49
  4. 3The two fast blinks3:22
  5. 4Steady red: a DC ground fault4:08
  6. 5What the FAQ adds: no light, and red flashing5:01
  7. 6Two trees, two questions6:06
  8. 7How it shows on the screen8:46
  9. 8Communication isn't production10:31
  10. 9The common mistake11:54
  11. 10Quick check12:38
  12. 11Checklist and next lesson13:09

Preview transcript

734 words

This is the text of the open part of this lesson. The full transcript comes with the course, along with the job site materials.

Intro

0:00

The system's been running for a month, and the homeowner calls: a micro disappeared from the portal. Disappearing from the portal is one thing. Stopping production is another. The manufacturer's guide separates the two. Hi, I'm Sol. This is lesson six point one, the first in the troubleshooting and warranty module. And I'm Helios. Today I show up with the service ticket open in my hand. Today's documents: the DS3 Series manual, with its LED table, and the manufacturer's troubleshooting guide for professional installers. Today I read the LED, and I read the screen. By the end of this lesson, you'll read the six LED states of the DS3, and know what each one asks for. And I'll tell communication from production by the LED and the guide's two trees, before I book the visit. And you'll close with a sentence for the homeowner: losing communication isn't losing production. Where do we start? The homeowner already sent me a photo of the roof. With the LED on the unit, the cheapest information there is. Then the two trees of the guide, and how each failure shows up on the portal.

The start: ten green blinks

1:25

Chapter one. DS3 Series user manual, revision two point three, page eighteen: status indications. The start-up LED: ten short green blinks when DC power is first applied to the microinverter. That's a successful microinverter startup. We saw that one in lesson two point two, at step seven. Page fourteen, step seven, says it too: the micro should immediately blink green ten times. And the whole check starts and ends within ten seconds of plugging in the unit. And page nineteen, after reconnecting the DC: a quick red, followed by ten short green flashes. Three places in the same manual, one count: ten. But there's that support sheet from lesson two point two, the one with three green blinks. That's the sheet for an inoperable microinverter, and it carries no revision number. It says three; the manuals say ten. The manuals govern: ten green blinks. That sheet is used for its checks, never for LED counts. And whoever counts on three takes a good micro for a bad one. Those blinks say startup. What happens after that, the operation LED says.

The two slow blinks

2:49

Chapter two. Same page eighteen, the operation LED. Flashing slow green, a five second gap: producing power and communicating with the ECU. Two pieces of news in a single blink: it produces, and it talks to the ECU. Flashing slow red, also a five second gap: not producing power. Same five seconds, green or red. The color says whether there's energy. Chapter three. Same page, the two fast lines.

The two fast blinks

3:22

Flashing fast green, a two second gap: not communicating with the ECU for over sixty minutes, but still producing power. That line saves trips. Fast green is data stopped, not energy stopped. Flashing fast red, also a two second gap: not communicating with the ECU for over sixty minutes, and not producing power. So the color talks about energy, and the speed talks about communication. Six states in all, counting the startup and the steady red. And the steady red is the one that changes my day. That's next. Chapter four. Same page eighteen, the GFDI error.

Steady red: a DC ground fault

4:08

Steady red: the default for DC side ground fault protection. A solid red LED means the microinverter detected a ground fault detector interrupter error, the GFDI, in the PV system. GFDI. And if I flip the breaker off and on, does it clear? No. Until the GFDI error is cleared, the LED stays red, and the ECU keeps reporting the fault. And the manual's line: contact your local APsystems technical support. So steady red isn't a communication problem, and it isn't shade. It's a fault with a physical cause. What to check before calling support, and how the error gets cleared, comes in lesson six point three.

What the FAQ adds: no light, and red flashing

5:01

Chapter five. Two more questions, from the APsystems installer FAQ. First one: the LED is off. Dead micro? The FAQ's answer: no sunshine, no DC input voltage. And then the LED shows no color. So an LED that's off with no sun says nothing about the micro. Second one: the red LED flashing. The FAQ starts with two checks, before you contact support. One: check that the operating voltage and frequency ranges match the grid requirement. Two: check that the breaker, the AC connector, and the Y connector are well connected.

After this lessonThe full course: 27 lessons in the order of the job

Job site materials in every lesson, questions inside the video, spaced review, a final exam and a certificate of completion with a public verification code. 7 days to cancel, with a full refund.