Micros per branch, the current and the breaker
The branch math by the NEC: 125 % of the output current, the breaker cap by wire size, and the DS3-S at 208 V, with the datasheet's 8 against the code's 7.
Every page cited is the page of the document's PDF file, not always the number printed on the page.
What this lesson solves
- The branch current is the sum of the output currents: six DS3 at 240 V are 6 × 3.7 A = 22.2 A.
- Inverter current is continuous: conductors and breakers carry 125 % of it (NEC 2017 690.8(B) and 705.60; NEC 2023 and NEC 2026 705.30(B)).
- Breaker cap of 240.4(D) in 2017, 2023 and 2026: 20 A on 12 AWG, 30 A on 10 AWG copper; never raise the breaker without the conductor.
- DS3-S at 208 V on 30 A: the datasheet prints 8, the code math gives 7, and the course teaches 7. The trunk's 28 A or 35 A is the third limit.
The numbers in this lesson, with sources
| What | Value | Fact |
|---|---|---|
| DS3 output current, 208 V and 240 V | 4.2 A and 3.7 A | 3.3 |
| DS3 per branch, 12 AWG and 20 A | 3 at 208 V; 4 at 240 V | 9.47 |
| DS3 per branch, 10 AWG and 30 A | 5 at 208 V; 6 at 240 V | 9.47 |
| DS3-S at 208 V, 10 AWG and 30 A | 7 (26.95 A); datasheet 8 (30.8 A) | 16.11 |
Each value comes from the course fact base, with the document page or the code section on record.
Chapters
- Intro0:00
- 1The output numbers1:19
- 2What the datasheet says2:33
- 3The NEC math3:40
- 4The discrepancy, out loud6:25
- 5Two-forty or two-oh-eight8:15
- 6Four models, one method9:39
- 7The wire and the voltage rise10:40
- 8The three limits15:32
- 9The common mistake16:05
- 10Quick check16:55
- 11Checklist and next lesson17:25
Preview transcript
973 wordsThis is the text of the open part of this lesson. The full transcript comes with the course, along with the job site materials.
Intro
0:00Eight DS3-S on one branch, at two-oh-eight. That's what the datasheet prints for ten AWG and a thirty-amp breaker. The answer isn't a guess. It comes from the NEC math, and the number it gives isn't eight. Hi, I'm Sol. This is lesson three point two, still on the AC side. And I'm Helios. I brought the branch somebody wants to fill to the top. Today we do the branch math, start to finish: the current, the wire, and the breaker. The two-pole breaker the manual calls bi-polar. Same part. By the end of this lesson, you'll size any DS3 branch the same way, with no exceptions. I want to walk out with a number, not with the feeling that it fits. You'll walk out with both: the number, and the page that backs it. Where do we start? With the datasheet's output numbers. Then its limit, the NEC math, and the difference between the two. Then two-forty or two-oh-eight, the four models, the wire, the voltage rise, and the three limits.
The output numbers
1:19Chapter one. The DS3 Series datasheet for the USA and Canada, revision two point three, page two, the output data. Maximum continuous output power of the DS3: eight hundred eighty volt-amps. Nominal output voltage: two hundred eight or two hundred forty volts, line to line. And the line that rules this lesson: nominal output current. Four point two amps at two-oh-eight, three point seven at two-forty. Four point two, or three point seven, per micro. That's the number I'm going to multiply. Right. The branch current is the sum of the output currents of the micros on that branch. In the drawing, the micros join in parallel along the same trunk cable. And the current adds up, all the way to the end that goes down to the junction box and the grid. Six DS3 at two-forty: six times three point seven, twenty-two point two amps. The datasheet calls it a branch. The NEC calls it the inverter output circuit. The same run of wire.
What the datasheet says
2:33Chapter two. Same page, the two lines that set the branch limit. Maximum units per twelve AWG branch with a twenty-amp breaker. For the DS3: three at two-oh-eight, four at two-forty. Per ten AWG branch with a thirty-amp breaker: five at two-oh-eight, six at two-forty. The wire size and the breaker, written right in the line. That helps. The manual repeats the same table, page twenty-two. And note two, at the bottom of the datasheet: limits may vary. Refer to local requirements for the number per branch. So the datasheet number is the manufacturer's. The number for the job comes from the local code. And the manual says the same about the breaker: bi-polar, with the appropriate rated current, or according to local regulations. Local requirements, local regulations. In the U.S., that has a name: the NEC edition your AHJ enforces.
The NEC math
3:40Chapter three. The NEC, the inverter output circuit. In the twenty seventeen text, section six ninety point eight. The circuit current is the inverter's continuous output current rating. And inverter currents are considered continuous. Continuous? The micro never goes above its nominal current. That's how the code treats it: continuous. So conductors and breakers carry not less than a hundred twenty-five percent of it. Only an assembly listed for continuous operation at a hundred percent may be used at a hundred percent. The rule is the same in the twenty twenty-three and twenty twenty-six editions, with new section numbers. The card shows them. And the twenty twenty-six edition lets that current be rounded to the nearest whole amp. No branch count of the series changes. Then the cap by wire size. Section two forty point four D: twenty amps for twelve AWG copper, thirty for ten AWG. Ten-gauge, a thirty-amp breaker at most. Twelve-gauge, twenty. Even if the wire could carry more. Even if it could. And the cap is the same in the twenty seventeen, twenty twenty-three and twenty twenty-six editions. Ask your AHJ which edition and which amendments apply. The method you're about to run holds in all three. So the math has three steps. One: add up the current of the micros on the branch. Two: multiply by one point two five. Three: compare with the breaker the wire size allows. Run it with the DS3 at two-forty, on ten AWG. Six DS3 at three point seven: twenty-two point two amps. Times one point two five: twenty-seven point seven five. Twenty-seven point seven five fits a thirty-amp breaker, the cap for ten AWG. It works. And a seventh? A seventh DS3 at two-forty takes it past thirty amps, with the margin. It doesn't fit. So six on ten AWG. And on twelve AWG? Four DS3 give eighteen point five amps with the margin. They fit the twenty-amp breaker. A fifth doesn't. The card has the math for every model of the series, at both voltages and on both wire sizes. That's the table I take to the job.
The discrepancy, out loud
6:25Chapter four. Put the datasheet and the math side by side. For the DS3, they give the same numbers. Three and four on twenty amps, five and six on thirty. Every cell of the series matches the math, except one. Which one? The DS3-S at two-oh-eight, on ten AWG with a thirty-amp breaker. The datasheet prints eight. Eight times three point oh eight is twenty-four point six four amps. Times one point two five: thirty point eight. Thirty point eight, with the margin, against a thirty-amp breaker. It doesn't fit. The math gives seven: twenty-six point nine five amps. That's the number the code backs. And the twenty twenty-six rounding changes nothing: twenty-five amps times one point two five is thirty-one point two five. So we say it once, out loud: the datasheet prints eight, the code math gives seven. This course teaches seven.
Job site materials in every lesson, questions inside the video, spaced review, a final exam and a certificate of completion with a public verification code. 7 days to cancel, with a full refund.